Honeywell VC7931NF6111T

Honeywell
VC7931NF6111T

Specifications


The specifications following are nominal and conform to generally accepted industry standards. Honeywell is not responsible for damages resulting from misapplication or misuse of its products.


Voltage:

  • Label Color Code 24V 50Hz; 24V 60Hz Models Blue 100-130 V 50-60 Hz Model Black 200-240 V 50-60 Hz Model Red
  • Power consumption: 6 Watts Max. at nominal Voltage (during valve position change). Use 24 V Class 2 transformer. Provide 6 VA per valve for transformer and connection wire sizing.
  • Maximum Duty Cycle: 15%
  • Nominal timing: Valve opens in 6 seconds @ 60 Hz (20% longer @ 50 Hz). VC8040 Series opens in 12 seconds @ 60 Hz (20% longer @ 50 Hz).
  • Electrical termination: Available in 3 versions: (1) Molex™ (header # 39-30-1060). Requires mating connector (receptacle/housing # 39-01-2060). OR (2) integral 1 meter [nominal 39″] lead wire cable. (3) 5 feet [1.5 meter] plenum-rated cable per UL94-5V. Includes plastic adapter for use with 3/8″ flexible conduit.
  • End switch rating: 2.2 A inductive from 5 to 110 Vac, 1.0 A inductive above 110 to 277 Vac. Min. DC switching capability: 5 mA @ 24 Vdc
  • Operating ambient temperature: 0 to 65°C [32 to 150°F] Except VC2114, VC2714, VC8114 & VC8714 are 0 to 60°C [32 to 140°F]
  • Humidity Rating: 5-95% RH (non-condensing)
  • Fluid temperatures: 34 to 203°F [1 to 95°C]
  • Shipping & storage temperature: -40 to +65°C [-40 to +150°F]
  • Atmosphere: non-corrosive, non-explosive